© 2009 Cypress Solutions PAD Operation (Revision 1.0)
11 Example Modem PAD Configuration
cmd padsvct 15 0 Set connection timeout to 15 seconds, maximum connection timer is disabled
(default settings, in effect after cmd factory)
cmd save Save configuration to modem’s non-volatile memory
cmd pwrmode 2 Power cycle
5.2 Modem PAD Configuration for a SCADA Master Device Polling a Single
Field Device in Slave Mode
In this example, a Chameleon modem is connected to a master device which polls data from a single field
device in slave mode. The field slave device is either connected to another Chameleon modem or has
built-in TCP/IP functionality. The master device is typically a server running a SCADA application and
communicates with the field device via a request/response protocol. The slave devices will only send
responses to requests sent.
The modem connected to a master device operates at a baud rate of 19200 with full hardware flow
control. The master device receives sentences on its serial port of maximum length 100 bytes (with no
common end character) which are to be sent to a single slave unit at IP address 100.100.1.2, port 5000.
The serial master device requires echoing of data that it sends to modem.
For the modem connected to the serial master device, enter the following commands from the serial
console: